On The Hill Child Care Center

4640 Nixon Park Drive, Syracuse, NY 13215License
F

Data Freshness & Provenance

Inspection coverage

24 inspections on record

Active providers

License status: License

Last refreshed

April 3, 2026

Latest inspection

February 4, 2026

Provenance

New York licensing inspections and DaycareCheck scoring

Quick Facts

These facts are normalized from the official record so they can be quoted directly.

Updated April 3, 2026

Provider
On The Hill Child Care Center
License number
45207
Location
4640 Nixon Park Drive, Syracuse, NY 13215
Status
License
Safety grade
F (Poor), score 33.8/100
Inspection record
24 inspections, last inspected February 4, 2026
Provenance
Official state licensing inspections and DaycareCheck scoring. Last refreshed April 3, 2026.

Safety Scorecard

F
Poor33.8 / 100
Health100/100
Safety0/100
Staffing0/100
Compliance25/100

80

Total Violations

Feb 4, 2026

Last Inspection

108

Capacity

Violation Timeline

Violations by month over the last 3 years, colored by severity.

All Violations (80)

SERIOUSSTAFFING418-1.14(c)May 2, 2025

Each staff person and volunteer must complete a minimum of thirty (30) hours of training every two years. The required thirty (30) hours of training every two years is subject to the following conditions:

Resolution: Corrected

SERIOUSSTAFFING418-1.14(d)May 2, 2025

Training must address all topics or subject matters required by state and federal law. The required state topics are:

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(iii)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from service personnel licensed by the New York State Department of State to perform fire alarm systems maintenance, repair and testing which shows that the fire alarm and detection systems have been inspected, tested and maintained during the current license period in accordance with the applicable requirements of the Fire and Building code of New York State or other applicable fire and building codes when the Fire and Building Code of New York State is not applicable, for use of the building as a child day care center;

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(iv)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from service personnel qualified to perform fire suppression systems testing showing that fire suppression equipment and systems have been tested and maintained during the current license period in accordance with the requirements of the Fire Code and Building Code of New York State, or other applicable fire and building codes when the Fire and Building Code of New York State is not applicable, for use of the building as a child day care center; and

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(v)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from an inspector from the New York State Department of Labor, or an insurance company licensed to write boiler insurance in New York State, showing that all steam or hot water boilers have been inspected and approved during the current license period in accordance with the requirements of the New York State Department of Labor. For all other fuel burning heating systems and equipment, and boilers not subject to the New York State Department of Labor requirements, documentation of service by a heating contractor performed within the 12 months preceding the date of application for renewal.

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(iv)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from service personnel qualified to perform fire suppression systems testing showing that fire suppression equipment and systems have been tested and maintained during the current license period in accordance with the requirements of the Fire Code and Building Code of New York State, or other applicable fire and building codes when the Fire and Building Code of New York State is not applicable, for use of the building as a child day care center; and

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(v)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from an inspector from the New York State Department of Labor, or an insurance company licensed to write boiler insurance in New York State, showing that all steam or hot water boilers have been inspected and approved during the current license period in accordance with the requirements of the New York State Department of Labor. For all other fuel burning heating systems and equipment, and boilers not subject to the New York State Department of Labor requirements, documentation of service by a heating contractor performed within the 12 months preceding the date of application for renewal.

Resolution: Corrected

SERIOUSSTAFFING418-1.14(c)May 2, 2025

Each staff person and volunteer must complete a minimum of thirty (30) hours of training every two years. The required thirty (30) hours of training every two years is subject to the following conditions:

Resolution: Corrected

SERIOUSSTAFFING418-1.14(d)May 2, 2025

Training must address all topics or subject matters required by state and federal law. The required state topics are:

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(iii)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from service personnel licensed by the New York State Department of State to perform fire alarm systems maintenance, repair and testing which shows that the fire alarm and detection systems have been inspected, tested and maintained during the current license period in accordance with the applicable requirements of the Fire and Building code of New York State or other applicable fire and building codes when the Fire and Building Code of New York State is not applicable, for use of the building as a child day care center;

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(iv)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from service personnel qualified to perform fire suppression systems testing showing that fire suppression equipment and systems have been tested and maintained during the current license period in accordance with the requirements of the Fire Code and Building Code of New York State, or other applicable fire and building codes when the Fire and Building Code of New York State is not applicable, for use of the building as a child day care center; and

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(v)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from an inspector from the New York State Department of Labor, or an insurance company licensed to write boiler insurance in New York State, showing that all steam or hot water boilers have been inspected and approved during the current license period in accordance with the requirements of the New York State Department of Labor. For all other fuel burning heating systems and equipment, and boilers not subject to the New York State Department of Labor requirements, documentation of service by a heating contractor performed within the 12 months preceding the date of application for renewal.

Resolution: Corrected

SERIOUSSTAFFING418-1.14(c)May 2, 2025

Each staff person and volunteer must complete a minimum of thirty (30) hours of training every two years. The required thirty (30) hours of training every two years is subject to the following conditions:

Resolution: Corrected

SERIOUSSTAFFING418-1.14(d)May 2, 2025

Training must address all topics or subject matters required by state and federal law. The required state topics are:

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(iii)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from service personnel licensed by the New York State Department of State to perform fire alarm systems maintenance, repair and testing which shows that the fire alarm and detection systems have been inspected, tested and maintained during the current license period in accordance with the applicable requirements of the Fire and Building code of New York State or other applicable fire and building codes when the Fire and Building Code of New York State is not applicable, for use of the building as a child day care center;

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(v)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from an inspector from the New York State Department of Labor, or an insurance company licensed to write boiler insurance in New York State, showing that all steam or hot water boilers have been inspected and approved during the current license period in accordance with the requirements of the New York State Department of Labor. For all other fuel burning heating systems and equipment, and boilers not subject to the New York State Department of Labor requirements, documentation of service by a heating contractor performed within the 12 months preceding the date of application for renewal.

Resolution: Corrected

SERIOUSSTAFFING418-1.14(c)May 2, 2025

Each staff person and volunteer must complete a minimum of thirty (30) hours of training every two years. The required thirty (30) hours of training every two years is subject to the following conditions:

Resolution: Corrected

SERIOUSSTAFFING418-1.14(d)May 2, 2025

Training must address all topics or subject matters required by state and federal law. The required state topics are:

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(iii)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from service personnel licensed by the New York State Department of State to perform fire alarm systems maintenance, repair and testing which shows that the fire alarm and detection systems have been inspected, tested and maintained during the current license period in accordance with the applicable requirements of the Fire and Building code of New York State or other applicable fire and building codes when the Fire and Building Code of New York State is not applicable, for use of the building as a child day care center;

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(iv)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from service personnel qualified to perform fire suppression systems testing showing that fire suppression equipment and systems have been tested and maintained during the current license period in accordance with the requirements of the Fire Code and Building Code of New York State, or other applicable fire and building codes when the Fire and Building Code of New York State is not applicable, for use of the building as a child day care center; and

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(v)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from an inspector from the New York State Department of Labor, or an insurance company licensed to write boiler insurance in New York State, showing that all steam or hot water boilers have been inspected and approved during the current license period in accordance with the requirements of the New York State Department of Labor. For all other fuel burning heating systems and equipment, and boilers not subject to the New York State Department of Labor requirements, documentation of service by a heating contractor performed within the 12 months preceding the date of application for renewal.

Resolution: Corrected

SERIOUSSTAFFING418-1.14(c)May 2, 2025

Each staff person and volunteer must complete a minimum of thirty (30) hours of training every two years. The required thirty (30) hours of training every two years is subject to the following conditions:

Resolution: Corrected

SERIOUSSTAFFING418-1.14(d)May 2, 2025

Training must address all topics or subject matters required by state and federal law. The required state topics are:

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(iii)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from service personnel licensed by the New York State Department of State to perform fire alarm systems maintenance, repair and testing which shows that the fire alarm and detection systems have been inspected, tested and maintained during the current license period in accordance with the applicable requirements of the Fire and Building code of New York State or other applicable fire and building codes when the Fire and Building Code of New York State is not applicable, for use of the building as a child day care center;

Resolution: Corrected

SERIOUSSAFETY418-1.15(b)(29)(iv)May 2, 2025

Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from service personnel qualified to perform fire suppression systems testing showing that fire suppression equipment and systems have been tested and maintained during the current license period in accordance with the requirements of the Fire Code and Building Code of New York State, or other applicable fire and building codes when the Fire and Building Code of New York State is not applicable, for use of the building as a child day care center; and

Resolution: Corrected

SERIOUSSAFETY418-1.5(a)Jan 16, 2025

Suitable precautions must be taken to eliminate all conditions in areas accessible to children which pose a safety or health hazard.

Resolution: Corrected

SERIOUSSAFETY418-1.5(a)Jan 16, 2025

Suitable precautions must be taken to eliminate all conditions in areas accessible to children which pose a safety or health hazard.

Resolution: Corrected

SERIOUSSAFETY418-1.5(a)Jan 16, 2025

Suitable precautions must be taken to eliminate all conditions in areas accessible to children which pose a safety or health hazard.

Resolution: Corrected

SERIOUSSAFETY418-1.5(a)Jan 16, 2025

Suitable precautions must be taken to eliminate all conditions in areas accessible to children which pose a safety or health hazard.

Resolution: Corrected

SERIOUSSAFETY418-1.5(a)Jan 16, 2025

Suitable precautions must be taken to eliminate all conditions in areas accessible to children which pose a safety or health hazard.

Resolution: Corrected

SERIOUSCOMPLIANCE418-1.3(d)Jan 15, 2025

A temperature of at least 68 degrees Fahrenheit must be maintained in all rooms to be occupied by children.

Resolution: Corrected

SERIOUSSAFETY418-1.5(y)Jan 15, 2025

Protective caps, covers or permanently installed obstructive devices must be used on all electrical outlets that are accessible to children.

Resolution: Corrected

SERIOUSSAFETY418-1.4(a)Jan 15, 2025

Suitable precautions must be taken to eliminate all conditions which may contribute to or create a fire hazard.

Resolution: Corrected

SERIOUSSAFETY418-1.4(f)(2)Jan 15, 2025

All corridors, aisles, and approaches to exits must be kept unobstructed at all times.

Resolution: Corrected

SERIOUSSAFETY418-1.5(a)Jan 15, 2025

Suitable precautions must be taken to eliminate all conditions in areas accessible to children which pose a safety or health hazard.

Resolution: Corrected

SERIOUSCOMPLIANCE418-1.3(d)Jan 15, 2025

A temperature of at least 68 degrees Fahrenheit must be maintained in all rooms to be occupied by children.

Resolution: Corrected

SERIOUSCOMPLIANCE418-1.3(d)Jan 15, 2025

A temperature of at least 68 degrees Fahrenheit must be maintained in all rooms to be occupied by children.

Resolution: Corrected

SERIOUSSAFETY418-1.4(a)Jan 15, 2025

Suitable precautions must be taken to eliminate all conditions which may contribute to or create a fire hazard.

Resolution: Corrected

SERIOUSSAFETY418-1.4(f)(2)Jan 15, 2025

All corridors, aisles, and approaches to exits must be kept unobstructed at all times.

Resolution: Corrected

SERIOUSSAFETY418-1.5(a)Jan 15, 2025

Suitable precautions must be taken to eliminate all conditions in areas accessible to children which pose a safety or health hazard.

Resolution: Corrected

SERIOUSSAFETY418-1.5(y)Jan 15, 2025

Protective caps, covers or permanently installed obstructive devices must be used on all electrical outlets that are accessible to children.

Resolution: Corrected

SERIOUSCOMPLIANCE418-1.3(d)Jan 15, 2025

A temperature of at least 68 degrees Fahrenheit must be maintained in all rooms to be occupied by children.

Resolution: Corrected

SERIOUSSAFETY418-1.4(a)Jan 15, 2025

Suitable precautions must be taken to eliminate all conditions which may contribute to or create a fire hazard.

Resolution: Corrected

SERIOUSSAFETY418-1.4(f)(2)Jan 15, 2025

All corridors, aisles, and approaches to exits must be kept unobstructed at all times.

Resolution: Corrected

SERIOUSSAFETY418-1.5(a)Jan 15, 2025

Suitable precautions must be taken to eliminate all conditions in areas accessible to children which pose a safety or health hazard.

Resolution: Corrected

SERIOUSSAFETY418-1.5(y)Jan 15, 2025

Protective caps, covers or permanently installed obstructive devices must be used on all electrical outlets that are accessible to children.

Resolution: Corrected

SERIOUSSAFETY418-1.4(a)Jan 15, 2025

Suitable precautions must be taken to eliminate all conditions which may contribute to or create a fire hazard.

Resolution: Corrected

SERIOUSSAFETY418-1.4(f)(2)Jan 15, 2025

All corridors, aisles, and approaches to exits must be kept unobstructed at all times.

Resolution: Corrected

SERIOUSSAFETY418-1.5(a)Jan 15, 2025

Suitable precautions must be taken to eliminate all conditions in areas accessible to children which pose a safety or health hazard.

Resolution: Corrected

SERIOUSSAFETY418-1.5(y)Jan 15, 2025

Protective caps, covers or permanently installed obstructive devices must be used on all electrical outlets that are accessible to children.

Resolution: Corrected

SERIOUSCOMPLIANCE418-1.3(d)Jan 15, 2025

A temperature of at least 68 degrees Fahrenheit must be maintained in all rooms to be occupied by children.

Resolution: Corrected

SERIOUSSAFETY418-1.4(a)Jan 15, 2025

Suitable precautions must be taken to eliminate all conditions which may contribute to or create a fire hazard.

Resolution: Corrected

SERIOUSSAFETY418-1.4(f)(2)Jan 15, 2025

All corridors, aisles, and approaches to exits must be kept unobstructed at all times.

Resolution: Corrected

SERIOUSSAFETY418-1.5(a)Jan 15, 2025

Suitable precautions must be taken to eliminate all conditions in areas accessible to children which pose a safety or health hazard.

Resolution: Corrected

SERIOUSSAFETY418-1.5(y)Jan 15, 2025

Protective caps, covers or permanently installed obstructive devices must be used on all electrical outlets that are accessible to children.

Resolution: Corrected

SERIOUSCOMPLIANCE418-1.3(a)(2)Jan 19, 2024

Whenever change(s), addition(s) or expansion(s) are proposed which will affect, or reasonably may be expected to affect, those portions of the building designated for the care of children or for their egress in case of an emergency, the licensee must receive written approval from the Office prior to initiating such change(s), addition(s), or expansion(s).

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(5)(i)Jan 19, 2024

for 4-year-old children: there must be one teacher for every eight children;

Resolution: Corrected

SERIOUSSAFETY418-1.8(l)(8)Jan 19, 2024

Except for Office approved continuity of care classrooms, children under three years of age may not participate in mixed age groups except for limited periods of time at the beginning and end of the child day care center's daily operation.

Resolution: Corrected

SERIOUSSAFETY418-1.8(l)(8)Jan 19, 2024

Except for Office approved continuity of care classrooms, children under three years of age may not participate in mixed age groups except for limited periods of time at the beginning and end of the child day care center's daily operation.

Resolution: Corrected

SERIOUSCOMPLIANCE418-1.3(a)(2)Jan 19, 2024

Whenever change(s), addition(s) or expansion(s) are proposed which will affect, or reasonably may be expected to affect, those portions of the building designated for the care of children or for their egress in case of an emergency, the licensee must receive written approval from the Office prior to initiating such change(s), addition(s), or expansion(s).

Resolution: Corrected

SERIOUSSAFETY418-1.8(l)(8)Jan 19, 2024

Except for Office approved continuity of care classrooms, children under three years of age may not participate in mixed age groups except for limited periods of time at the beginning and end of the child day care center's daily operation.

Resolution: Corrected

SERIOUSCOMPLIANCE418-1.3(a)(2)Jan 19, 2024

Whenever change(s), addition(s) or expansion(s) are proposed which will affect, or reasonably may be expected to affect, those portions of the building designated for the care of children or for their egress in case of an emergency, the licensee must receive written approval from the Office prior to initiating such change(s), addition(s), or expansion(s).

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(5)(i)Jan 19, 2024

for 4-year-old children: there must be one teacher for every eight children;

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(5)(i)Jan 19, 2024

for 4-year-old children: there must be one teacher for every eight children;

Resolution: Corrected

SERIOUSCOMPLIANCE418-1.3(a)(2)Jan 19, 2024

Whenever change(s), addition(s) or expansion(s) are proposed which will affect, or reasonably may be expected to affect, those portions of the building designated for the care of children or for their egress in case of an emergency, the licensee must receive written approval from the Office prior to initiating such change(s), addition(s), or expansion(s).

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(5)(i)Jan 19, 2024

for 4-year-old children: there must be one teacher for every eight children;

Resolution: Corrected

SERIOUSSAFETY418-1.8(l)(8)Jan 19, 2024

Except for Office approved continuity of care classrooms, children under three years of age may not participate in mixed age groups except for limited periods of time at the beginning and end of the child day care center's daily operation.

Resolution: Corrected

SERIOUSCOMPLIANCE418-1.3(a)(2)Jan 19, 2024

Whenever change(s), addition(s) or expansion(s) are proposed which will affect, or reasonably may be expected to affect, those portions of the building designated for the care of children or for their egress in case of an emergency, the licensee must receive written approval from the Office prior to initiating such change(s), addition(s), or expansion(s).

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(5)(i)Jan 19, 2024

for 4-year-old children: there must be one teacher for every eight children;

Resolution: Corrected

SERIOUSSAFETY418-1.8(l)(8)Jan 19, 2024

Except for Office approved continuity of care classrooms, children under three years of age may not participate in mixed age groups except for limited periods of time at the beginning and end of the child day care center's daily operation.

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(3)(i)Dec 4, 2023

for children between ages 18 months old and 36 months old: there must be one teacher for every five children;

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(5)(i)Dec 4, 2023

for 4-year-old children: there must be one teacher for every eight children;

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(3)(i)Dec 4, 2023

for children between ages 18 months old and 36 months old: there must be one teacher for every five children;

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(3)(i)Dec 4, 2023

for children between ages 18 months old and 36 months old: there must be one teacher for every five children;

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(5)(i)Dec 4, 2023

for 4-year-old children: there must be one teacher for every eight children;

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(3)(i)Dec 4, 2023

for children between ages 18 months old and 36 months old: there must be one teacher for every five children;

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(5)(i)Dec 4, 2023

for 4-year-old children: there must be one teacher for every eight children;

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(3)(i)Dec 4, 2023

for children between ages 18 months old and 36 months old: there must be one teacher for every five children;

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(5)(i)Dec 4, 2023

for 4-year-old children: there must be one teacher for every eight children;

Resolution: Corrected

SERIOUSSAFETY418-1.8(k)(5)(i)Dec 4, 2023

for 4-year-old children: there must be one teacher for every eight children;

Resolution: Corrected

Get Inspection Alerts

Be the first to know when new inspections or violations are reported for On The Hill Child Care Center.

Nearby Daycares in Syracuse

Frequently Asked Questions

What is On The Hill Child Care Center's safety grade?

On The Hill Child Care Center has a safety grade of F (Poor) based on state inspection data. The composite score is 33.8 out of 100.

How many violations does On The Hill Child Care Center have?

On The Hill Child Care Center has 80 total violations on record, including 0 critical, 80 serious, and 0 minor.

When was On The Hill Child Care Center last inspected?

On The Hill Child Care Center was last inspected on February 4, 2026.

Parent Resources