Endwell United Methodist Church
Data Freshness & Provenance
Inspection coverage
20 inspections on record
Active providers
License status: License
Last refreshed
April 1, 2026
Latest inspection
February 10, 2026
Provenance
New York licensing inspections and DaycareCheck scoring
Quick Facts
These facts are normalized from the official record so they can be quoted directly.
Updated April 1, 2026
- Provider
- Endwell United Methodist Church
- License number
- 883562
- Location
- 3301 Watson Blvd, Endwell, NY 13760
- Status
- License
- Safety grade
- F (Poor), score 55.0/100
- Inspection record
- 20 inspections, last inspected February 10, 2026
- Provenance
- Official state licensing inspections and DaycareCheck scoring. Last refreshed April 1, 2026.
Safety Scorecard
27
Total Violations
Feb 10, 2026
Last Inspection
34
Capacity
Violation Timeline
Violations by month over the last 3 years, colored by severity.
All Violations (36)
Fire detection, alarm and firefighting equipment appropriate to the type of building construction, size, height and occupancy must be provided, maintained and operate as designed.
Resolution: Corrected
Fire detection, alarm and firefighting equipment appropriate to the type of building construction, size, height and occupancy must be provided, maintained and operate as designed.
Resolution: Corrected
Fire detection, alarm and firefighting equipment appropriate to the type of building construction, size, height and occupancy must be provided, maintained and operate as designed.
Resolution: Corrected
Fire detection, alarm and firefighting equipment appropriate to the type of building construction, size, height and occupancy must be provided, maintained and operate as designed.
Resolution: Corrected
Evacuation drills must be conducted at least monthly during various hours of operation of the child day care center.
Resolution: Corrected
Each program must hold two shelter-in-place drills annually during which procedures and supplies are reviewed. Parents must be made aware of this drill in advance.
Resolution: Corrected
Evacuation drills must be conducted at least monthly during various hours of operation of the child day care center.
Resolution: Corrected
Each program must hold two shelter-in-place drills annually during which procedures and supplies are reviewed. Parents must be made aware of this drill in advance.
Resolution: Corrected
Evacuation drills must be conducted at least monthly during various hours of operation of the child day care center.
Resolution: Corrected
Evacuation drills must be conducted at least monthly during various hours of operation of the child day care center.
Resolution: Corrected
Each program must hold two shelter-in-place drills annually during which procedures and supplies are reviewed. Parents must be made aware of this drill in advance.
Resolution: Corrected
Each program must hold two shelter-in-place drills annually during which procedures and supplies are reviewed. Parents must be made aware of this drill in advance.
Resolution: Corrected
Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from an inspector from the New York State Department of Labor, or an insurance company licensed to write boiler insurance in New York State, showing that all steam or hot water boilers have been inspected and approved during the current license period in accordance with the requirements of the New York State Department of Labor. For all other fuel burning heating systems and equipment, and boilers not subject to the New York State Department of Labor requirements, documentation of service by a heating contractor performed within the 12 months preceding the date of application for renewal.
Resolution: Corrected
Each staff person and volunteer must complete a minimum of thirty (30) hours of training every two years. The required thirty (30) hours of training every two years is subject to the following conditions:
Resolution: Corrected
Each applicant for, or individual in the position of director, teacher, or volunteer must complete Office-approved training that complies with federal minimum health and safety pre-service or three-month orientation period requirements. This training must be obtained pre-service or within three months of starting such position.
Resolution: Corrected
Each applicant for, or individual in the position of director, teacher, or volunteer must complete Office-approved training that complies with federal minimum health and safety pre-service or three-month orientation period requirements. This training must be obtained pre-service or within three months of starting such position.
Resolution: Corrected
Each staff person and volunteer must complete a minimum of thirty (30) hours of training every two years. The required thirty (30) hours of training every two years is subject to the following conditions:
Resolution: Corrected
Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from an inspector from the New York State Department of Labor, or an insurance company licensed to write boiler insurance in New York State, showing that all steam or hot water boilers have been inspected and approved during the current license period in accordance with the requirements of the New York State Department of Labor. For all other fuel burning heating systems and equipment, and boilers not subject to the New York State Department of Labor requirements, documentation of service by a heating contractor performed within the 12 months preceding the date of application for renewal.
Resolution: Corrected
Each applicant for, or individual in the position of director, teacher, or volunteer must complete Office-approved training that complies with federal minimum health and safety pre-service or three-month orientation period requirements. This training must be obtained pre-service or within three months of starting such position.
Resolution: Corrected
Each staff person and volunteer must complete a minimum of thirty (30) hours of training every two years. The required thirty (30) hours of training every two years is subject to the following conditions:
Resolution: Corrected
Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from an inspector from the New York State Department of Labor, or an insurance company licensed to write boiler insurance in New York State, showing that all steam or hot water boilers have been inspected and approved during the current license period in accordance with the requirements of the New York State Department of Labor. For all other fuel burning heating systems and equipment, and boilers not subject to the New York State Department of Labor requirements, documentation of service by a heating contractor performed within the 12 months preceding the date of application for renewal.
Resolution: Corrected
Each applicant for, or individual in the position of director, teacher, or volunteer must complete Office-approved training that complies with federal minimum health and safety pre-service or three-month orientation period requirements. This training must be obtained pre-service or within three months of starting such position.
Resolution: Corrected
Each staff person and volunteer must complete a minimum of thirty (30) hours of training every two years. The required thirty (30) hours of training every two years is subject to the following conditions:
Resolution: Corrected
Mid-point requirements for four-year license holders. At the two-year calendar date in a four year licensing cycle, a program must be in compliance with the following mid-point requirements and be able to show proof of compliance to the Office when requested, as follows: documentation from an inspector from the New York State Department of Labor, or an insurance company licensed to write boiler insurance in New York State, showing that all steam or hot water boilers have been inspected and approved during the current license period in accordance with the requirements of the New York State Department of Labor. For all other fuel burning heating systems and equipment, and boilers not subject to the New York State Department of Labor requirements, documentation of service by a heating contractor performed within the 12 months preceding the date of application for renewal.
Resolution: Corrected
Suitable precautions must be taken to eliminate all conditions which may contribute to or create a fire hazard.
Resolution: Corrected
The program must maintain on file at the child day care center, available for inspection by the Office or its designees at any time, the following records in a current and accurate manner: children's individual health care plans; parental consents for emergency medical treatment; child's medical statement, immunizations, and any available results of lead screening for children not yet enrolled in kindergarten or a higher grade only; the name and dosage of any medications used by a child, the frequency of administration of such medications, and a record of their administration by child care center staff; daily health check documentation; a record of illnesses and injuries occurring while in care; and any indicators of child abuse or maltreatment;
Resolution: Corrected
Portable electric heaters or other portable heating devices, regardless of the type of fuel used, may not be used in child day care centers.
Resolution: Corrected
Suitable precautions must be taken to eliminate all conditions which may contribute to or create a fire hazard.
Resolution: Corrected
Portable electric heaters or other portable heating devices, regardless of the type of fuel used, may not be used in child day care centers.
Resolution: Corrected
The program must maintain on file at the child day care center, available for inspection by the Office or its designees at any time, the following records in a current and accurate manner: children's individual health care plans; parental consents for emergency medical treatment; child's medical statement, immunizations, and any available results of lead screening for children not yet enrolled in kindergarten or a higher grade only; the name and dosage of any medications used by a child, the frequency of administration of such medications, and a record of their administration by child care center staff; daily health check documentation; a record of illnesses and injuries occurring while in care; and any indicators of child abuse or maltreatment;
Resolution: Corrected
Suitable precautions must be taken to eliminate all conditions which may contribute to or create a fire hazard.
Resolution: Corrected
Portable electric heaters or other portable heating devices, regardless of the type of fuel used, may not be used in child day care centers.
Resolution: Corrected
Suitable precautions must be taken to eliminate all conditions which may contribute to or create a fire hazard.
Resolution: Corrected
The program must maintain on file at the child day care center, available for inspection by the Office or its designees at any time, the following records in a current and accurate manner: children's individual health care plans; parental consents for emergency medical treatment; child's medical statement, immunizations, and any available results of lead screening for children not yet enrolled in kindergarten or a higher grade only; the name and dosage of any medications used by a child, the frequency of administration of such medications, and a record of their administration by child care center staff; daily health check documentation; a record of illnesses and injuries occurring while in care; and any indicators of child abuse or maltreatment;
Resolution: Corrected
Portable electric heaters or other portable heating devices, regardless of the type of fuel used, may not be used in child day care centers.
Resolution: Corrected
The program must maintain on file at the child day care center, available for inspection by the Office or its designees at any time, the following records in a current and accurate manner: children's individual health care plans; parental consents for emergency medical treatment; child's medical statement, immunizations, and any available results of lead screening for children not yet enrolled in kindergarten or a higher grade only; the name and dosage of any medications used by a child, the frequency of administration of such medications, and a record of their administration by child care center staff; daily health check documentation; a record of illnesses and injuries occurring while in care; and any indicators of child abuse or maltreatment;
Resolution: Corrected
Get Inspection Alerts
Be the first to know when new inspections or violations are reported for Endwell United Methodist Church.
Nearby Daycares in Endwell
Boczulak, Bonnie
300 Norton Ave.
Children's Home of Wyoming Conference
3618 Briar Ln
Arnold, Amy
3100 Buckingham Road
Future Faces Child Care & Learning Center Inc.
800 Hooper Road
Northminster Preschool
711 Farm to Market Road
Frequently Asked Questions
What is Endwell United Methodist Church's safety grade?
Endwell United Methodist Church has a safety grade of F (Poor) based on state inspection data. The composite score is 55.0 out of 100.
How many violations does Endwell United Methodist Church have?
Endwell United Methodist Church has 27 total violations on record, including 0 critical, 27 serious, and 0 minor.
When was Endwell United Methodist Church last inspected?
Endwell United Methodist Church was last inspected on February 10, 2026.