KAI MING RAINBOW INFANT/TODDLER CENTER

799 PACIFIC AVENUE, San Francisco, CA 94133LICENSED
A

Data Freshness & Provenance

Inspection coverage

5 inspections on record

Active providers

License status: LICENSED

Last refreshed

April 3, 2026

Latest inspection

May 2, 2025

Provenance

California licensing inspections and DaycareCheck scoring

Quick Facts

These facts are normalized from the official record so they can be quoted directly.

Updated April 3, 2026

Provider
KAI MING RAINBOW INFANT/TODDLER CENTER
License number
Not listed
Location
799 PACIFIC AVENUE, San Francisco, CA 94133
Status
LICENSED
Safety grade
A (Excellent), score 95.5/100
Inspection record
5 inspections, last inspected May 2, 2025
Provenance
Official state licensing inspections and DaycareCheck scoring. Last refreshed April 3, 2026.

Safety Scorecard

A
Excellent95.5 / 100
Health100/100
Safety85/100
Staffing100/100
Compliance100/100

3

Total Violations

May 2, 2025

Last Inspection

22

Capacity

Violation Timeline

Violations by month over the last 3 years, colored by severity.

All Violations (3)

SERIOUSSAFETY101700.3(b)(1)ComplaintMar 1, 2024

Type B citation - potential risk if not corrected

SERIOUSSAFETY101700.3(b)(1)Type BComplaintMar 1, 2024

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25On March 01, 2024 at approximately 12:00pm, Licensing Program Analyst (LPA) Ly conducted an unannounced, case management inspection for the Action Level Exceedance (ALE) of Lead in Child Care Center's water. LPA met with Site Manager, Iokchan Lei. The purpose of the inspection was explained. Facility is an infant/toddler facility. Present during today's visit were 4 staff caring for 9 infants and 4 other staff caring 12 toddlers. LPA discussed the new Assembly Bill (AB) 2370, Chapter 676, Statutes of 2018 requires the Lead Testing of water in the Child Care Center with the site director during the inspection. All Child Care Centers that are located in buildings constructed before January 1, 2010, must have their water tested and post the results by January 1, 2023, and every 5 years after the date of the first testing. The facility received the ALE report from the Vendor on 06/14/2022. Test results for this facility that exceeded a higher level of parts per billion (ppb) allowed, 5.5ppb. The facility was proactive putting signs indicating that the water outlets and sinks are "not for drinking" and for "hand washing only." The facility took action to contact the facility's management to repair and replace the fixtures. Per Site Manager, the affected fixture B located in the toddler classroom with the lead test result 8.5 is currently being used for hand washing only. Fixture D with the lead test result 6.4 is also being used for hand washing only. Facility with lead test results higher than 5.5ppb poses a potential health and safety risks to persons in care. Type B violation is being issued on this day in accordance with WD101700.3. See LIC 809D for deficiency cited. During today's visit, LPA obtained the copies of the Facility Sketch (LIC999), Analytical Report dated 06/13/2022. A copy of this report and appeal rights were discussed and left with Site Manager whose signature on this form confirm receipt of these reports. Notice of Site Visit was posted. Notice to remain posted for 30 days. SUPERVISORS NAME: Garfield Leung LICENSING EVALUATOR NAME: Winnie Ly LICENSING EVALUATOR SIGNATURE: DATE: 03/01/2024 I acknowledge receipt of this form and understand my licensing appeal rights as explained and received. FACILITY REPRESENTATIVE SIGNATURE: DATE: 03/01/2024 This report must be available at Child Care and Group Home facilities for public review for 3 years. LIC809 (FAS) - (06/04)Page: 1 of 2 FACILITY NAME: KAI MING RAINBOW INFANT/TODDLER CENTER FACILITY NUMBER: 384002725 DEFICIENCY INFORMATION FOR THIS PAGE: VISIT DATE: 03/01/2024 Deficiency Type POC Due Date / Section NumberDEFICIENCIESPLAN OF CORRECTIONS(POCs) Type B 04/01/2024 Section Cited 101700.3(b)(1) 1 2 3 4 5 6 7101700.3 California Lead Action Level at Child Care Centers (b)(1) A result with values of 5.5 ppb or greater shall be deemed an Action Level Exceedance. This requirement was not met as evidenced by: 1 2 3 4 5 6 7The facility has put up signs at affected fixtures indicating that the water outlets are not for drinking and are strictly for hand washing only. 8 9 10 11 12 13 14Based on observation, interview and record review, the facility did not ensure to maintain a level to be under 5 ppb at fixtures B and D. This poses a potential health, safety or personal rights risk to persons in care. 8 9 10 11 12 13 14Facility must have running water for Faucet B and D until fixtures are retested with a certified water sampler by 03/01/2024. Once retest is done, faciity representative will submit retest results to the department. 1 2 3 4 5 6 71 2 3 4 5 6 7 1 2 3 4 5 6 71 2 3 4 5 6 7 Failure to correct the cited deficiency(ies), on or before the Plan of Correction (POC) due date, may result in a civil penalty assessment. SUPERVISOR'S NAME:Garfield Leung LICENSING EVALUATOR NAME:Winnie Ly LICENSING EVALUATOR SIGNATURE: DATE: 03/01/2024 I acknowledge receipt of this form and understand my appeal rights as explained and received. FACILITY REPRESENTATIVE SIGNATURE: DATE: 03/01/2024

SERIOUSSAFETY101700.3(b)(1)Type BComplaintMar 1, 2024

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25On March 01, 2024 at approximately 12:00pm, Licensing Program Analyst (LPA) Ly conducted an unannounced, case management inspection for the Action Level Exceedance (ALE) of Lead in Child Care Center's water. LPA met with Site Manager, Iokchan Lei. The purpose of the inspection was explained. Facility is an infant/toddler facility. Present during today's visit were 4 staff caring for 9 infants and 4 other staff caring 12 toddlers. LPA discussed the new Assembly Bill (AB) 2370, Chapter 676, Statutes of 2018 requires the Lead Testing of water in the Child Care Center with the site director during the inspection. All Child Care Centers that are located in buildings constructed before January 1, 2010, must have their water tested and post the results by January 1, 2023, and every 5 years after the date of the first testing. The facility received the ALE report from the Vendor on 06/14/2022. Test results for this facility that exceeded a higher level of parts per billion (ppb) allowed, 5.5ppb. The facility was proactive putting signs indicating that the water outlets and sinks are "not for drinking" and for "hand washing only." The facility took action to contact the facility's management to repair and replace the fixtures. Per Site Manager, the affected fixture B located in the toddler classroom with the lead test result 8.5 is currently being used for hand washing only. Fixture D with the lead test result 6.4 is also being used for hand washing only. Facility with lead test results higher than 5.5ppb poses a potential health and safety risks to persons in care. Type B violation is being issued on this day in accordance with WD101700.3. See LIC 809D for deficiency cited. During today's visit, LPA obtained the copies of the Facility Sketch (LIC999), Analytical Report dated 06/13/2022. A copy of this report and appeal rights were discussed and left with Site Manager whose signature on this form confirm receipt of these reports. Notice of Site Visit was posted. Notice to remain posted for 30 days. SUPERVISORS NAME: Garfield Leung LICENSING EVALUATOR NAME: Winnie Ly LICENSING EVALUATOR SIGNATURE: DATE: 03/01/2024 I acknowledge receipt of this form and understand my licensing appeal rights as explained and received. FACILITY REPRESENTATIVE SIGNATURE: DATE: 03/01/2024 This report must be available at Child Care and Group Home facilities for public review for 3 years. LIC809 (FAS) - (06/04)Page: 1 of 2 FACILITY NAME: KAI MING RAINBOW INFANT/TODDLER CENTER FACILITY NUMBER: 384002725 DEFICIENCY INFORMATION FOR THIS PAGE: VISIT DATE: 03/01/2024 Deficiency Type POC Due Date / Section NumberDEFICIENCIESPLAN OF CORRECTIONS(POCs) Type B 04/01/2024 Section Cited 101700.3(b)(1) 1 2 3 4 5 6 7101700.3 California Lead Action Level at Child Care Centers (b)(1) A result with values of 5.5 ppb or greater shall be deemed an Action Level Exceedance. This requirement was not met as evidenced by: 1 2 3 4 5 6 7The facility has put up signs at affected fixtures indicating that the water outlets are not for drinking and are strictly for hand washing only. 8 9 10 11 12 13 14Based on observation, interview and record review, the facility did not ensure to maintain a level to be under 5 ppb at fixtures B and D. This poses a potential health, safety or personal rights risk to persons in care. 8 9 10 11 12 13 14Facility must have running water for Faucet B and D until fixtures are retested with a certified water sampler by 03/01/2024. Once retest is done, faciity representative will submit retest results to the department. 1 2 3 4 5 6 71 2 3 4 5 6 7 1 2 3 4 5 6 71 2 3 4 5 6 7 Failure to correct the cited deficiency(ies), on or before the Plan of Correction (POC) due date, may result in a civil penalty assessment. SUPERVISOR'S NAME:Garfield Leung LICENSING EVALUATOR NAME:Winnie Ly LICENSING EVALUATOR SIGNATURE: DATE: 03/01/2024 I acknowledge receipt of this form and understand my appeal rights as explained and received. FACILITY REPRESENTATIVE SIGNATURE: DATE: 03/01/2024

Get Inspection Alerts

Be the first to know when new inspections or violations are reported for KAI MING RAINBOW INFANT/TODDLER CENTER.

Nearby Daycares in San Francisco

Frequently Asked Questions

What is KAI MING RAINBOW INFANT/TODDLER CENTER's safety grade?

KAI MING RAINBOW INFANT/TODDLER CENTER has a safety grade of A (Excellent) based on state inspection data. The composite score is 95.5 out of 100.

How many violations does KAI MING RAINBOW INFANT/TODDLER CENTER have?

KAI MING RAINBOW INFANT/TODDLER CENTER has 3 total violations on record, including 0 critical, 3 serious, and 0 minor.

When was KAI MING RAINBOW INFANT/TODDLER CENTER last inspected?

KAI MING RAINBOW INFANT/TODDLER CENTER was last inspected on May 2, 2025.